ENVIROMUX-16D

Large Enterprise Environment Monitoring System

ENVIROMUX-16D

Product Highlights

  • 16 external configurable sensors, 8 digital inputs, 4 output relays
  • Configure Smart Alerts for different event combinations
  • User-programmable IP camera snapshots
  • Linux inside
  • Connect to an Ethernet network
  • Cascade up to 5 units via RS485 serial &/or Ethernet connection (1 master, 4 slaves)
  • Triggered Events can send SSH commands to soft shutdown or reboot machines

The ENVIROMUX® Large Enterprise Environment Monitoring System (ENVIROMUX-16D) monitors critical environmental conditions, such as temperature, humidity, liquid water presence, power, intrusion, and smoke. When a sensor goes out of range of a configurable threshold, the system will notify you via email, LEDs, alarm beacon, siren, web page, network management (SNMP), voice phone calls (via Automatic Voice Dialer System), and SMS messages (via external USB 3G modem).

The system includes three internal sensors: temperature, humidity and power. It also supports 16 external configurable sensors, eight digital input sensors, and four output relays for control of external devices.

  • Monitor and manage server room environmental and security conditions over IP.
  • Sensors supported:
    • 16 external configurable sensors
    • 8 digital inputs sensitive to contact closure
    • 3 internal sensors – temperature, humidity, power
    • 8 Remote Temperature/Humidity Sensors over IP
      • E-MICRO-T: 1 integrated temperature sensor, 2 RJ45 ports for external temperature/humidity sensors, 2 digital inputs sensitive to contact closure, dual DC power (dual redundancy).
      • E-MICRO-TRHP: 1 integrated temperature/humidity combination sensor, 2 RJ45 ports for external temperature/humidity sensors, 2 digital inputs sensitive to contact closure, built-in Power over Ethernet (POE), dual DC power (triple redundancy).
  • Four output relays for control of external devices.
    • Relay activates upon alarm or via the user interface.
    • Control output relays via SNMP SET commands to power on/off external devices.
  • Supports IP network video cameras for live view of any facility.
    • One integrated view – see different Web cameras side-by-side with physical and environmental parameters.
    • Any programmed event can trigger a snapshot from an IP camera.
  • Monitor (ping) up to 64 IP network devices.
    • Alerts are sent if devices are not responding
  • Linux inside.
  • Create multiple alerts for any installed sensor.
  • Sensor conditions (events) can be configured to trigger alerts by themselves, and/or be used in combination with other events to trigger Smart Alerts.
    • Configure up to 50 events.
      • Setup SSH commands to be sent when events are triggered to soft shutdown or reboot machines.
    • Up to 20 Smart Alerts can be configured to use different event combinations to send alert messages.
  • Alerts are posted in message log, which is accessible through Web user interface.
  • Automatically configures network settings received from a connected DHCP server.
    • If a DHCP server is not found, the default static IP address will be used.
  • Integrates with various Open Source monitoring packages – Nagios and MRTG.
    • The unit can be polled via SNMP.
  • USB ports for connecting USB modem or for downloading log data to USB flash drive.
  • Internal battery backup.
    • Alerts are sent when there is a power outage and when power returns.
  • Available with optional dual power for connection to two separate power sources.
  • Up to five units can be connected via Ethernet connection or using CAT5 expansion cables to increase the number of sensors connected.
    • Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
      • Each master and slave unit needs its own unique IP address.
    • Cascade up to four E-16D units as slaves to one E-16D master unit using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
      • Each slave unit needs its own unique RS485 address value that can range from 1-255.
    • Uses a single Web interface for all systems/sensors connected.
  • Available with optional 48VDC or 24VDC power.
  • Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 E-2D/5D/16D, E-SEMS-16(U), IPDU-S4/8 units and all connected sensors.
  • 1RU rack mount case is standard.
    • The ENVIROMUX system can be mounted so that the sensor connectors are facing the front or back of the rack.
  • Security: HTTPS, SSHv2, SSLv3, IP Filtering, LDAPv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
  • Multi-language support – English, German, Chinese, and Japanese.
  • Use in data centers, co-lo sites, web hosting facilities, telecom switching sites, POP sites, server closets, or any unmanned area that needs to be monitored.

1. Power Port
  • 100 to 240 VAC at 50 or 60 Hz via IEC connector. (Country-specific power supply cable included.)
  • Power consumption: 35W
  • Connection for Earth Ground.
  • Fuse protection.
  • Optional 48VDC power (not shown).
    • Accepts 36~72VDC (48VDC nominal).
  • Optional 24VDC power (not shown).
    • Accepts 20~32VDC (24VDC nominal).
  • Optional dual power (not shown).
    • Available on AC, 48VDC, and 24VDC models.
    • If the first power source fails, the unit will automatically, without interruption, switch over to the second power source before switching to the battery backup.
2. RJ45 Sensor Ports
  • Sixteen RJ45 modular jacks for connecting NTI temperature, humidity, temperature/humidity, liquid detection, smoke detection, glass break, vibration and motion sensors.
3. Digital Inputs
  • Eight screw terminals pairs for connecting dry contact devices.
  • Input voltage: 0VDC to +25VDC.
  • Provides +12VDC, 50mA for terminals 1-7, and +12VDC, 350mA for terminal 8 only.
  • Fuse protection.
4. Digital Outputs
  • Four screw terminals pairs.
  • Potential-free relay switch contacts.
  • Normally open / normally closed connection points.
  • Maximum switching load: 0.5A at 100VAC, 1A at 30VDC, 0.5A at 48VDC.
5. Beacon Port
  • One screw terminal pair.
  • Provides +12VDC, 180 mA to supply an alarm beacon.
  • Fuse protection
6. Siren Port
  • One screw terminal pair.
  • Provides +12VDC, 180 mA to supply a siren.
  • Fuse protection
7. AUX Power
  • One screw terminal pair.
  • Provides 12VDC, 150mA.
8. USB Device Ports
  • Four female USB Type A connectors for connecting USB modem or for downloading log data to USB flash drive.
    • Two USB ports on front panel and 2 on back panel.
9. USB Console Port
  • One female USB Type B connector for connecting a PC for serial terminal access.
10. RS232 (DCS) Port
  • One female RJ45 serial port for terminal access.
11. Ethernet Port
  • One 10/100 Base-T Ethernet port with RJ45 Ethernet connector.
    • Supports full- and half-duplex.
12. RS232 AUX Port
  • One RJ45 port for connecting a serial GSM modem or a remote serially-controlled device.
13. Cascade In/Out Ports
  • Two RJ45 jacks.
  • A maximum of 5 systems can be used in a cascaded configuration via RS485 to increase the number of sensor ports (1 master, 4 slaves).
    • Each slave unit needs its own unique RS485 address value that can range from 1-255.
    • Use CAT5/5e/6 patch cables with RJ45 connectors wired straight through
    • Up to 4,000 feet between the master unit and the slave unit.
    • The last slave must have a terminating plug (E-TRMPLG, not included) in the empty socket.
  • Uses a single Web interface for all systems connected.
Protocols
  • HTTP/HTTPS, SNMP V1/V2c/V3, SMTP, TCP/IP, Syslog, SNTP, DHCP, SSHv2, SSLv3, TLS v1.2, LDAPv3, XOAUTH2, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour, IPV6, WAP 2.0, RADIUS
    • Support for XOAUTH2 provides higher security authentication for email accounts (e.g. Gmail).
  • Compatible with any SNMP management software.
    • The unit can be polled via SNMP.
  • Operates and configures via HTTP/HTTPS web page, Telnet, SSH, or USB/RJ45 serial interface.
  • An IP address can be assigned to the E-16D automatically by a DHCP server.
  • Generates SNMP traps, email alerts, syslog messages, and SMS messages (via USB 3G modem).
    • Alerts are posted in event log, which is accessible through Web user interface.
    • Email alerts can be sent to 17 addresses.
      • Users can configure the schedule for when they will be alerted, as well as customize the e-mail subject line for each sensor alert.
    • SNMP traps have unique OID’s (Object Identifiers) for each sensor.
      • OIDs for sensor and contact values for E-16D are available.
Internal Temperature Sensor
  • Applications from 32 to 104°F (0 to 40°C).
  • Accurate to within ±1.35°F (±0.75°C).
Internal Humidity Sensor
  • Applications from 20% to 80% relative humidity at temperatures between 32 to 104°F (0 to 40°C).
  • Accurate to within ±5% relative humidity.
Internal Power Sensor
  • Measures mains voltage: 0 to 255 VAC
  • Measures battery voltage: 0 to 20 VDC
  • Measures voltage on 24VDC models: 20 to 32VDC
  • Measures voltage on 48VDC models: 36 to 72VDC
  • Alerts are sent when there is a power outage and when power returns.
Back-up Battery
  • Rechargeable sealed lead-acid battery.
    • Battery removal/disposal instructions area available in the download sections
  • Provides back-up for one hour.
MTBF
  • E-16D: 39,685 hours.
Dimensions
  • WxDxH (all options):
    • Without supplied rackmount kit: 16.19×10.01×1.75″
    • With supplied rackmount kit: 19×10.01×1.75″
Weight
  • E-16D: 9.5 lb (4.31 kg).
  • E-16D-48VDP: 9.6 lbs (4.36 kg).
Environmental
  • Operating temperature: 32 to 104°F (0 to 40°C).
  • Storage temperature: -22 to 140°F (-30 to 60°C).
  • Operating /Storage Relative Humidity: 17 to 90% non-condensing RH.
Regulatory Approvals
  • CE, RoHS
Web Interface
  • Configuration can be done over the Internet/LAN or 3G data connection via Web page.
    • 3G data connection requires a USB 3G modem with a data plan.
      • Email and SMS alerts can be sent through the modem instead of the Ethernet connection.
  • Supports Internet Explorer 6.0 and higher, Firefox 1.5 and higher, Netscape 9, Google Chrome, Safari 1.3 and higher for MAC, and Safari 3.0 and higher for PC.
  • Configure sensor thresholds, alarm methods, formats of alerts, and system data log.
    • Customize SMS messages and email subject headers for sensor alerts.
  • View/edit sensors’ current values, thresholds and alert statuses.
    • All sensors connected, including up to 8 Remote Temperature/Humidity Sensors over IP, to the E-16D can be viewed on one summary page.
    • All sensors in alert can be quickly viewed on the alert summary page to enable timely responses.
    • User configurable settings allow sensors to return to normal status when alert condition clears, without manually acknowledging/dismissing the alert.
  • View/edit entries stored in the system logs.
    • Event log records system events such as alerts, user login/logout, failed email messages, etc.
    • Data log records samples of sensor readings. User specified sampling time period.
    • Both the event log and the data log store up to 1,000 entries.
    • The log can be downloaded as a tab-delimited plain text file.
  • Configure IP information (address, subnet mask, default gateway, DNS, etc.), user administrative settings, and data logging settings.
  • Upload custom x509 certificates.
  • Up to 16 users can access the web page at one time.
  • Permissions, schedule and alert methods are configurable for each user.
  • Configure up to 50 sensor conditions (events).
  • Configure up to 20 Smart Alerts to use different event combinations to send alert messages.
  • Up to five units can be used together to increase the number of sensors connected.
    • Cascade up to four E-2D/5D/16D units as slaves to one E-2D/5D/16D master unit via Ethernet connection.
      • Each master and slave unit needs its own unique IP address.
      • IP sensors can only be connected to a master unit.
    • E-16D slave units can also be configured as RS485 local slave units using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
      • Each slave unit needs its own unique RS485 address value that can range from 1-255.
      • The last slave must have a terminating plug (not included) in the empty socket.
    • Uses a single Web interface for all systems/sensors connected.
  • Multi-language support – English, German, Chinese, and Japanese.
Front Panel Interface
  • LEDs indicate the following:
    • “INT ALERT” – internal sensor goes out of range of a configurable threshold.
    • “EXT ALERT” – external sensor goes out of range of a configurable threshold.
    • “LOW BAT” – backup battery is low.
    • “CHECK LOG” – message is posted to the log.
    • “AUX” – indicates Auxiliary device is powered.
    • “PWR” – indicates system is powered.
  • Alarm Test/Silence button – use to test or silence the alarm connected to the siren terminals
  • Restore Defaults button – use to manually restore the E-16D back to factory settings.
  • System Reset button – use to manually reboot/restart the firmware for the E-16D.
Serial Interface / Telnet / SSH
  • Configure, control and monitor over the text-based menu system accessible via USB console port, RJ45 serial port, Telnet, and SSH.
    • Serial baud rate: 9,600 to 115,200bps.
    • Data format: 1 start bit, 8 data bits, no parity, 1 stop bit.
  • Access is controlled via username/password.
    • System stores encrypted login information.
  • Two user levels: user and administrator.
  • Multi-language support – English, German, Chinese, and Japanese.
  • Telnet and SSH can be enabled or disabled.
    • Network Security Enhancement: Disabling Telnet can prevent unsecure text menu access to the E-16D.
Network Operation
  • Automatically configures network settings received from a connected DHCP server.
    • If a DHCP server is not found, the default static IP address will be used.
  • SNMP support, allowing integration into network management platforms.
    • Control output relays via SNMP SET commands to power on/off external devices.
      • SET command can be sent from SNMP software, MIB browser (Windows), or command line (Linux).
  • Updating the system firmware.
Open Source Monitoring Integration
  • SNMP Plugin for Nagios
  • NTI SNMP Plugin for Zabbix
  • Using Multi Router Traffic Grapher (MRTG).
  • Data Logging using Syslog
Optional Management Software
  • Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 E-2D/5D/16D, E-MICRO-T(RHP), E-1W(P), E-SEMS-16(U), IPDU-S4/8 units and all connected sensors.
  • Push configuration changes to multiple connected units in a group at once.
    • E.g. new users, mail server, network settings, security settings, system settings, etc.
Mobile Summary Page (view product demo)
  • View summary page on mobile devices – smartphones, tablets, etc.
  • Summary page lists all connected sensors’ current values and alert statuses.
Optional Android App for Tablet/Phone
  • Optional Android App provides an easy-to-use interface for monitoring and displaying sensor statuses from one E-2D/5D/16D.

Sensors & Accessories – Sold Separately
Environmental Sensors
  • Remote Temperature/Humidity Sensor over IP
  • Temperature Sensors
  • RTD Temperature Transmitters/Sensors
  • Temperature/Humidity Sensors
  • Industrial Temperature/Humidity Sensors
  • Rope-Style Leak Detectors
  • Spot Leak Detectors
  • Under Carpet & Tape-Style Detectors
  • Liquid Level Float Switches
  • Ultrasonic Level Transmitter
  • Smoke Detectors
  • Gas Detectors
  • Air Flow/Velocity Detectors
  • Outdoor Temperature Sensor
  • Wind Speed Sensor
  • Barometric Pressure Transmitter
  • Pressure Sensors
Power Relays & Sensors
  • Power Over Ethernet Adapters
  • AC Voltage Detectors
  • AC & DC Power Monitors
  • Hall-Effect Sensors
  • 3-Phase Power Monitors/Transducers
  • Current Transformers
Security Sensors & Access Control
  • Door Contact Sensors
  • Vibration & Glass Break Sensors
  • Motion Sensors
  • Tamper Switch
  • Emergency/Panic Button
  • Access Control
Alert & Communication Accessories
  • Automatic Voice Dialer Systems
  • USB Modems
  • IP Surveillance Cameras
  • Siren Alarms
  • Alarm Beacons
  • Triggerable Audio Players
Sensor Accessories
  • Digital Input/Output Expanders
  • Fiber Converter/Extender
  • Sensor Converters – 4-20mA, 5VDC
  • Sensor Cables
  • Surge Protectors
  • Intrinsically Safe Barrier
Optional Replacement Back-up Battery
  • Data Sheet