ENVIROMUX-IPDU
Securely control power on/off/reboot to a server, router, web cam, firewall or other remote devices over IP.

ENVIROMUX-IPDU
Product Highlights
- Power on/off/reboot
- Configure up to 3 additional IP aliases that allow remote control of the unit through different networks
- Linux inside
- IPV 6 Compatible
- Shut down power when high temperature and other threats detected
The ENVIROMUX® Secure Remote Power Control Unit allows you to remotely reboot and control power (on/off) to up to eight servers or other powered devices from any location via secure web interface, RS232, SSH, or Telnet.
- Three operating modes for power reboot:
- Manual – select the outlet and turn the power on/off.
- Scheduled – set date/time/duration of power cycle.
- Associated – power on/off a device when a sensor goes out of range of a user-defined threshold, or reboot unresponsive IP devices.
- Security: HTTPS, SSHv2, SSLv3, TLS (4/8-port models only), IP Filtering, LDAPv3, AES 256-bit encryption, 16-character username/password authentication, user account restricted access rights.
- Configure, control and monitor the unit via Web interface or Command Line Interface (CLI).
- Up to 3 additional IP aliases can be configured to allow remote control of the unit using different networks.
- No scripts required – simply add the IP address, network mask, and gateway configurations through the web interface.
- The first network (default network) will be used for total control of the unit, i.e. inbound and outbound connections.
- The three other networks will allow web/SSH/telnet access only, i.e. inbound access only.
- Up to four separate networks can be plugged into a network switch that is linked to the unit to facilitate the configuration.
- Current, line voltage, line frequency, power factor monitoring (4/8-port models only).
- Supports two environmental sensors, including: temperature/humidity and water detection.
- Shut down power when high temperature and other environmental threats are detected.
- Monitor (ping) up to eight IP network devices.
- Sends alert notifications via email, syslog, LEDs, Web page, and SNMP.
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- Integrates with various Open Source monitoring packages – Nagios and MRTG.
- The unit can be polled via SNMP.
- Up to 17 units can be connected via Ethernet connection or using CAT5 expansion cables to increase the number of outlets and sensors connected (4- and 8-port models only).
- Cascade up to 16 IPDU-Sx units as slaves to one IPDU-Sx master unit via Ethernet connection.
- Each master and slave unit needs its own unique IP address.
- Cascade up to 16 IPDU-Sx units as slaves to one IPDU-Sx master unit using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- Uses a single Web interface for all systems/sensors connected.
- Cascade up to 16 IPDU-Sx units as slaves to one IPDU-Sx master unit via Ethernet connection.
- Overload protection via circuit breaker (4/8-port models only).
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 E-2D/5D/16D, E-SEMS-16(U), IPDU-S4/8 units and all connected sensors.
- Meets the electrostatic discharge (ESD) immunity requirements of IEC/EN 61000-4-2
- Features Normally Open (NO) relay contacts.
- The 4/8-port units are available with optional Normally Closed (NC) relay contacts.
- Optional industrial unit for harsh environments at temperatures from -40° to 158°F (-40° to 70°C).
Power
- 90 to 250 VAC at 50 to 60 Hz.
- Input Connector:
- IPDU-S2: IEC 320-C14 inlet
- IPDU-Sx-P15(-OT3): NEMA 5-15P line cord (US)
- IPDU-Sx-P10(-OT3): IEC 320-C14 inlet (EURO)
- Output Connectors: IEC C13 outlets.
- IPDU-S2: IEC 320-C13 outlets
- IPDU-Sx-P15(-OT3): NEMA 5-15R outlets (US)
- IPDU-Sx-P10(-OT3): IEC 320-C13 outlets (EURO)
NTI Part # | Input/Output | Location |
---|---|---|
IPDU-S2 | 10A | All |
IPDU-Sx-P15 | 15A | US/Canada |
IPDU-Sx-P10 | 10A | Euro/UK |
RJ45 Sensor Ports
- Two RJ45 modular jacks for connecting NTI temperature/humidity and liquid detection sensors.
- Available sensors
Network Interface
- One 10/100 Base-T Ethernet port with RJ45 Ethernet connector.
Console Port
- One female RJ45 port for terminal access.
Cascade In/Out Ports (4/8-Port Models)
- Two RJ45 jacks.
- A maximum of 17 systems can be used in a cascaded configuration via RS485 to increase the number of outlets and sensor ports (1 master, 16 slaves).
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- Use CAT5/5e/6 patch cables with RJ45 connectors wired straight through
- Up to 1,000 feet between the master unit and the slave unit.
- The last slave must have a terminating plug (E-TRMPLG, not included) in the empty socket.
USB Port (4/8-Port Models)
- Female USB Type A connector for downloading log data to USB flash drive.
Environmental
- IPDU-S2, IPDU-Sx-P15/P10:
- Operating temperature: 32 to 122°F (0 to 50°C).
- Storage temperature: -13 to 149°F (-25 to 65°C).
- IPDU-Sx-P15/P10-OT3:
- Operating temperature: -40 to 158°F (-40 to 70°C).
- Storage temperature: -40 to 185°F (-40 to 85°C).
- Operating/storage relative humidity: 0 to 90% non-condensing RH.
NTI Part # | MTBF (hrs) |
---|---|
IPDU-S2 | 183,724 |
IPDU-S4-P15 | 113,296 |
IPDU-S4-P10 | 86,017 |
IPDU-S8-P15 | 83,790 |
IPDU-S8-P10 | 57,051 |
Protocols
- HTTPS, SSHv2, SSLv3, TLS (4/8-port models only), LDAPv3, AES 256-bit, 3DES, Blowfish, RSA, EDH-RSA, Arcfour, SNMPv2c; IP filtering, IPV6
- Operates and configures via HTTP/HTTPS web page, Telnet, SSH, or RS232 interface.
- Alerts are sent using email, syslog, and/or SNMP traps.
- Alerts are posted in event log, which is accessible through Web user interface.
Regulatory Approvals
- CE, RoHS
- EN51055, EN50121-3-2
Web Interface
- Configure, control and monitor via HTTP/HTTPS webpage.
- Configure outlet operation settings, sensor thresholds and timing, alarm methods, alert formats, sensor/IP device outlet association, and system data log.
- Add up to 3 additional IP aliases that allow remote control of the unit through different networks.
- No scripts required – simply add the IP address, network mask, and gateway configurations through the web interface.
- The first network (default network) will be used for total control of the unit, i.e. inbound and outbound connections.
- The three other networks will allow web/SSH/telnet access only, i.e. inbound access only.
- View outlet status, sensor values, IP device values, and alert status on one summary page.
- View, Edit, Turn On/Off, Cycle buttons for each power outlet.
- View and Edit sensors and IP devices.
- View entries stored in the system logs.
- Event log records system events such as alerts, user login/logout, failed email messages, etc.
- Data log records samples of sensor readings. User specifies sampling time period.
- The log can be downloaded as a tab-delimited plain text file.
- Configure IP information, SMTP settings, SNMP settings, IP filtering, and user administrative settings.
- Upload custom x509 certificates (4/8-port models only).
- Administrate up to 15 users plus a root administrator.
- Configure permissions, schedule and alert methods for each user.
- Up to 17 units can be used together to increase the number of sensors connected.
- Cascade up to 16 IPDU-Sx units as slaves to one IPDU-Sx master unit via Ethernet connection.
- Each master and slave unit needs its own unique IP address.
- IPDU-Sx slave units can also be configured as RS485 local slave units using CAT5/5e/6 patch cables with RJ45 connectors wired straight through.
- Each slave unit needs its own unique RS485 address value that can range from 1-255.
- The last slave must have a terminating plug (not included) in the empty socket.
- Uses a single Web interface for all systems/sensors connected.
- Cascade up to 16 IPDU-Sx units as slaves to one IPDU-Sx master unit via Ethernet connection.
RS232/Telnet/SSH
- Configure, control and monitor over the text-based menu system accessible via RS232, Telnet, and SSH.
- Access is controlled via username/password.
- System stores encrypted login information.
- Two user levels: user and administrator.
Front Panel LED Indicators
- “POWER” (green) – indicates device is powered.
- “OUTLET” (green / red) – outlet is on or off.
- “SENSOR FAULT” (red) – lights up if a sensor goes out of range of a configurable threshold.
- “IP FAULT” (red) – lights up if an IP device is unresponsive.
Network Operation
- Automatically configures network settings received from a connected DHCP server.
- If a DHCP server is not found, the default static IP address will be used.
- Integrates with various Open Source monitoring packages – Nagios and MRTG.
- The unit can be polled via SNMP.
Open Source Monitoring Integration
- SNMP Plugin for Nagios
- NTI SNMP Plugin for Zabbix
- Using Multi Router Traffic Grapher.
Optional Management Software
- Optional intuitive graphical management software provides an easy-to-use, unified interface for both monitoring and configuring up to 3,000 E-2D/5D/16D, E-SEMS-16(U), IPDU-S4/8 units and all connected sensors.
- Data Sheet